Custom microprocessor controlled for highest accuracy and reliability. |
• |
3 LEDs for checking correct wiring status. |
• |
0 and 180 degree phase angle switch permits quick tests and consistent readings. |
• |
Digital read-out of tripping time. |
• |
Constant current source circuitry ensures that a fluctuating mains voltage does not affect the accuracy of readings. |
• |
Large custom digital display readout. |
• |
Visual indication of reversed phase and neutral wiring at socket. |
• |
Designed to IP54 Rating. |
• |
Complies with IEC 61557 |
• Test of a large kind of RCD's: Standard, Selective, AC and A (DC sensitive breakers)
|
|
Rated Tripping Current |
|10/20/30/200/300/500mA |
Fault Condition Settings |
|× 1/2, × 1, × 5, × DC,
|AUTO RAMP |
Trip Current Duration |
|1000ms, 200ms (×5) |
Lowest Resolution |
|1ms |
Trip Time Accuracy |
|±0.6%rdg±4dgt |
Operating Voltage |
|230V+10%-15%
|(195V~253V) 50Hz |
Safety Standard |
|IEC 61557-1,-6
|IEC 61010-1 CAT.III 300V
|IEC 61010-2-031 Pollution Degree 2 |
Withstand Voltage |
|3700V AC for 1 minute |
IP Rating |
|IEC 60529-IP54 |
Dimensions |
|186(L) × 167(W) × 89(D)mm |
Weight |
|800g approx. |
Accessories |
|Molded plug test leads
|Pouch for test leads
|Shoulder Strap
|Instruction Manual |
Optional |
|7121B (Simplified measurement probe) |
|
|